Schneider Electric's Mark Deguara: Liquid Cooling Readiness Must Be Verified Per Row; Hall-Level Headroom Cannot Be Directly Promised to AI Tenants
Imagine a new cloud tenant requesting a colocation provider in Western Sydney, Australia, to deploy a row of liquid-cooled GPU racks within an occupied data center. On paper, the site has spare floor space and backup electrical capacity. However, before quoting rack density or delivery dates, the operator must confirm whether the target row can support the new load while ensuring that existing tenants continue to receive their contracted services. In an assessment method published by Mark Deguara, Head of Technology Innovation at Schneider Electric, in November 2026, it is pointed out that liquid cooling readiness is specific to a particular rack row, not a general indicator for the entire hall.
This judgment changes the way capacity commitments are verified. Mark Deguara requires operators to confirm six dimensions per row: the sustained and peak electrical loads of the racks, the proportion of heat captured by the liquid loop versus the remaining air-cooling needs, the coolant temperature, flow, and pressure requirements, the complete electrical path from the grid connection to the rack distribution (including UPS and protection settings), floor loading and installation access (including the impact of CDU maintenance space on the number of leasable rack positions), and retrofit economics. In the Western Sydney case study, the central chiller plant may have overall headroom, but the branch serving the target row lacks sufficient flow during peak demand—a constraint that only becomes apparent through per-row verification.
Heat rejection verification must be conducted under local summer design conditions and planned maintenance states. Direct-to-chip cooling captures heat from high-power components via cold plates, while liquid-to-liquid Coolant Distribution Units (CDUs) transfer this heat to the facility water system. Operators must confirm the available temperature, flow, and differential pressure at the connection point while existing tenants are drawing cooling, and compare the CDU supplier's water quality requirements with the building-side filtration conditions. For rows without access to building cooling water, Heat Dissipation Units (HDUs) reject heat back into the room air; in this scenario, the room cooling system must simultaneously handle the heat discharged by the HDU and the residual heat from the cold plates. In mixed halls, rear door heat exchangers can intercept hot rack exhaust where the existing water system and rack configuration support them.
Retrofit economics depend on shared infrastructure and tenant deployment plans. Mark Deguara recommends comparing three options—targeted retrofit, dedicated hybrid zones, and independent expansion—using the same load and service conditions. If pipe routing, floor loading, or the outage required for grid integration makes live retrofitting unfeasible, prefabricated modular IT pods serve as an alternative option. Highly customized AI-fit facilities are difficult to repurpose after the lease expires, which impacts residual value assumptions. Acceptance records should capture the tested capacity, operational limits, and responsibility boundaries on both sides of the rack connection; the tenant agreement defines services based on this foundation rather than on the hall's nominal figures.
Sources :Schneider Electric Blog